BACring DPM-M1E Fieldbus Module

Description

The DPM-M1E fieldbus module is used for controlling and evaluating the end positions of motorized fire protection and smoke extraction dampers. Communication with the BACring DPB-Buscontroller is carried out via the BACring bus protocol. In addition to the bistable relay output, the two digital inputs are used to transmit feedback signals indicating the damper end positions. Furthermore, motor current monitoring is performed. The result is returned as a logical value on bit position I3. Thanks to its spring-loaded terminals, the module is completely maintenance-free and enables fast and secure wiring.

For applications with increased requirements regarding functional integrity, the DPM-M1E fieldbus module can be integrated into the DPH-Fire Safety-E90 enclosure. In combination with the DPH-Fire Safety-E90 enclosure, the DPM-M1E fieldbus module fulfills the requirements of DIN EN 1363-1:2020-05 for functional integrity in accordance with Section 5.3.1 of MLAR 2005 and thus achieves the required functional integrity of at least 90 minutes.

Download PDF Datasheet
DPM-M1E Fieldbus Module

Connection diagram

Further information

Bus voltage
20V DC +/- 2% (via DPB-Buscontroller)
Power supply motors
0 - 250V AC/DC
Display
Green LED as status display “BUS Activity”
Motor current detection
available
Controls
Test button motor 1
Bus protocol
  • BACring protocol
  • Set the outputs within 90 msec
  • Query the inputs within < 1.5 sec (regardless of the size of the ring bus)
Digital inputs
2 digital inputs for the potential-free limit switches (not isolated)
Relay output motor
1 relay output (bistable changeover contact), galvanically isolated, loadable up to 1A / 250V
Motor circuit fuse
1 A / medium time-lag 5x20mm fuse
Connections
  • Bus ports: WAGO spring-loaded terminal blocks type 236, light gray
  • Inputs and motor outputs: WAGO spring-loaded terminals type 236, dark gray
  • Motor supply: Phoenix Contact TFKC 2.5/4-ST-5.08 (4-pin, for looping through the motor supply)
EMC conformity
2014/35/EU, EN61000-6-1, EN61000-6-3, EN61000-4-2..-5
Maintenance
Maintenance-free
Assembly
Wall mounting
Temperature
0° to +75°C
Air humidity
  • Stored: 0% - 100%, non-condensing
  • Operation: 0% - 100%, non-condensing
Safety class
IP 66 (M20, M25 without screws)
Dimensions (W x H x D)
130 mm x 75 mm x 130 mm
Housing
Spelsberg (TK PS 1313-7-tm)
Weight
Approx. 0.4 kg
Download PDF Datasheet